PD688-0K0 for Hazardous Locations
5 digit 15.2 mm[0.6"] loop back-lit powered meter with Custom Engineering Units.
FM Type 4X, IP65; panel gasket provided
- 4-20 mA Input
- 5 Digit Display
- 0.6" (15.2 mm) LCD
- FM Type 4X, IP65 Front
- Shallow Depth Case 3.2" Behind Panel
- 2 V Drop (5.7 V with Backlight)
- Loop-Powered Backlight
- Custom Engineering Units
- Bargraph Display & Trend Arrow
- Maximum & Minimum Display
- Square Root, or Programmable Exponent
- Non-Volatile Memory - No Battery Needed
- Operating Temperature Range: -30 to 65°C
- Intrinsically Safe & Non-Incendive
- HART Protocol Transparent
This attractive meter also has a bar graph and trend arrow.
Programmable to display input as Linear, Square Root, or Programmable
Exponent or even Minimum and Maximum values.
Nema 4X enclosures available 3 Years warranty - parts and labor
Works to very cold temperatures
PD688 Approvals for Hazardous Locations
FM Approved & CSA Certified as intrinsically safe with entity for
use in Class I, Div 1, Groups ABCD; Class II, Div 1, Groups EFG;
Class III, Div 1; Class I, Zone 0, Group IIC; T-code = T4.
Non-incendive: Suitable for use in Class I, Div 2, Groups ABCD;
Class II, Div 2, Groups FG; Class III, Div 2.
Entity Parameters: Ui: 30 V; Ii: 175 mA; Ci: 0; Li: 0; Pi: 1.0 W
Note: Installation must be performed in accordance with Control Drawing LIM688-2
| Extreme cold operation |
|---|
Temperature
| -30°C | -35°C | -37°C | -40°C |
| Contrast | Very Good | Good | Poor | Poor |
| Approximate Update Time | 9 sec | 15
sec | 25-28 sec | 40-46 sec |
|---|
| Note: For optimum cold
temperature performance, set the “contrast” to
max, increase the “filter” setting, and set
“bypass” to minimum
(advanced menu, see manual).
|
If
you want a lesser priced meter without the approvals for Hazardous Locations see the PD683-
0K0
We can supply NEMA 4x Enclosures for this meter.
|