24Vdc @ 2.4A Regulated power supply
If you use this with our BVUPS (Battery Voltage
Uninterruptible Power-supply) make sure to mention the fact in your
order. Always measure the actual current of your load - most
manufacture specifications are for worst case and padded for legal
reasons. For details about sizing batteries see the
Battery application page.
Specifications
Remote voltage sense to eliminate line drop and improve regulation. Low
Output Ripple
UL, CSA, and TÜV Approvals
Mean Time Before Failure (MTBF) in Excess of 300,000 Hours
CE marked to Low Voltage Directive (LVD).
Input Frequency AC input. 47 63 Hz
3.0mVPK-PK plus 0.02% of output voltage, max Full load, 20MHz bandwidth.
Agency Approvals
UL1950.
CSA 1402 or CSA 22.2 No. 234/950. Approved
EN60950 (TÜV).
Dielectric Withstand Input to output. 3750 VRMS Voltage Input to ground. 3750
Electromagnetic FCC CFR title 47 Part 15 Sub-Part J - conducted.
Interference EN55022 / CISPR 22 conducted. Compatible with system compliance to
Level B.
EN55022 / CISPR 22 radiated.
Leakage Current Per EN60950 (264VAC) 23 50 mA
ENVIRONMENTAL SPECIFICATIONS
Dimensions : 4.00 X 4.87 X 1.62 Inches drawing
Operating Temperature Derate output power linearly above 50°C by 3% per °C.
At 100% load 0 50 °C
At 40% load 70 °C
Storage Temperature -40 85 °C
Temperature Coefficient 0°C to 50°C (after 15 minute warm-up). 0.1 0.3 %/°C
24 hours after warm-up. -0.3 +0.3 %
Shock Operating. 20 GPK
Vibration Random vibration from 10Hz to 2kHz, 3 axis. 6.15 GRMS
Note R10 = 2K for 27.6V
|